1.
Materials (Basel) ; 15(3)2022 Jan 28.
Artículo en Inglés | MEDLINE | ID: mdl-35160965

RESUMEN

The radiant floor system market is growing rapidly because Europe is moving toward a low-carbon economy and increased awareness about environmental sustainability and energy efficiency, stimulated by the ambitious EU Energy Efficient Directive and nZEB challenge. The high growth rate of the market share is due to the involvement of homeowners in the specifications of their living commodities, so they are thus willing to invest more at the initial stage to obtain long-term benefits and lower energy exploration costs. We performed an experimental campaign over three slabs with a hydronic radiant floor system of equal dimensions, shape, and pipe pitch with different screed mortar formulations to assess their performance throughout a heating/cooling cycle. The temperature at different heights within the interior of the screed mortars and at the surface were monitored. The results revealed that an improved screed mortar has a relevant impact on the efficiency of the system. Moreover, a three-dimensional transient heat transfer model was validated using the experimental data. The model was used to evaluate the impact of different finishing materials, namely wood, cork, ceramic, and linoleum, on the floor surface temperatures. The results showed differences of 15% in the surface temperature when using different floor finishing solutions.